Choice of standard outputs
Wide range isolated DC input supply
DIN Rail mounting
Signal Conditioned AC Average RMS or DC measurement output
On board bar graph display
User adjustable zero offset and span controls
Zero insertion loss in current measurement path
Earth leakage via differential Ipn for nominal Input ‘01’
Delivery in 3-5 days for small qty, Otherwise 4-6 weeks
Oztherm Part Number | F921-X-XX-DC-XX-XX |
Functions | Single Phase AC Current Transducer |
Supply Voltage | 9-36VDC |
Nominal Measurement Range | 0-20000 Amp (Sensor dependant) |
Maximum Measurement Range | 0-20000 Amp with External Sensor |
Alarm | C/O Relay 4Amp @ 30VDC, 0.5Amp @ 150VAC |
Response Time | 250mS |
Accuracy @ 25 Deg C | Class 1 |
Bandwidth | DC - 1kHz |
linearity | < 0.15% |
Isolation | 2.5kV |
Comms | N/A |
Weight | 250g |
Enclosure Size | 79 x 60 x 85mm |
Factory Pack Qty | 1 |
EU Directives | N/A |
Safety | Protection Class II 600V rms, installation category II 300V rms, installation category III Pollution Degree 2 in compliance with SIST EN 61010-1:2002 |
Enclosure Material | Polyamide non combustable-self-extinguishability, complying with UL 94 V-0 |
Enclosure Protection | IP40 |
Shock Withstand | 300g 8ms Pulse . 6 Shocks in each of 3 axes |
Vibration Withstand | 0.7g, 3...100Hz, 1oct/min 10 cycles in each of three axes |
Operating Temperature | -20 →+70 °C |